Source code for instrument.utils.controls_setup

"""
EPICS & ophyd related setup
===========================

.. autosummary::
    ~oregistry
    ~set_control_layer
    ~set_timeouts
    ~epics_scan_id_source
    ~connect_scan_id_pv
"""

import logging

import ophyd
from ophyd.signal import EpicsSignalBase
from ophydregistry import Registry

from ..configs.loaders import iconfig

logger = logging.getLogger(__name__)
logger.info(__file__)

re_config = iconfig.get("RUN_ENGINE", {})

DEFAULT_CONTROL_LAYER = "PyEpics"
DEFAULT_TIMEOUT = 60  # default used next...
ophyd_config = iconfig.get("OPHYD", {})


[docs] def epics_scan_id_source(scan_id_epics, _md): """ Callback function for RunEngine. Returns *next* scan_id to be used. * Ignore metadata dictionary passed as argument. * Get current scan_id from PV. * Apply lower limit of zero. * Increment (so that scan_id numbering starts from 1). * Set PV with new value. * Return new value. Exception will be raised if PV is not connected when next ``bps.open_run()`` is called. """ new_scan_id = max(scan_id_epics.get(), 0) + 1 scan_id_epics.put(new_scan_id) return new_scan_id
[docs] def connect_scan_id_pv(RE, pv: str = None): """ Define a PV to use for the RunEngine's `scan_id`. """ from ophyd import EpicsSignal pv = pv or re_config.get("SCAN_ID_PV") if pv is None: return logger.info("Using EPICS PV %r for RunEngine 'scan_id'", pv) scan_id_epics = EpicsSignal(pv, name="scan_id_epics") # Setup the RunEngine to use the EPICS PV to provide the scan_id. RE.scan_id_source = epics_scan_id_source(scan_id_epics) scan_id_epics.wait_for_connection() RE.md["scan_id_pv"] = scan_id_epics.pvname RE.md["scan_id"] = scan_id_epics.get() # set scan_id from EPICS
[docs] def set_control_layer(control_layer: str = DEFAULT_CONTROL_LAYER): """ Communications library between ophyd and EPICS Channel Access. Choices are: PyEpics (default) or caproto. OPHYD_CONTROL_LAYER is an application of "lessons learned." Only used in a couple rare cases where PyEpics code was failing. It's defined here since it was difficult to find how to do this in the ophyd documentation. """ control_layer = ophyd_config.get("CONTROL_LAYER", control_layer) ophyd.set_cl(control_layer.lower()) logger.info("using ophyd control layer: %r", ophyd.cl.name)
[docs] def set_timeouts(): """Set default timeout for all EpicsSignal connections & communications.""" if not EpicsSignalBase._EpicsSignalBase__any_instantiated: # Only BEFORE any EpicsSignalBase (or subclass) are created! timeouts = ophyd_config.get("TIMEOUTS", {}) EpicsSignalBase.set_defaults( auto_monitor=True, timeout=timeouts.get("PV_READ", DEFAULT_TIMEOUT), write_timeout=timeouts.get("PV_WRITE", DEFAULT_TIMEOUT), connection_timeout=iconfig.get("PV_CONNECTION", DEFAULT_TIMEOUT), )
oregistry = Registry(auto_register=True) """Registry of all ophyd-style Devices and Signals."""